Access Control System: Components and How It Works
An access control system decides who can open which door, and when. Every system, from one office door to a whole campus, is built from the same parts: a credential, a reader, a controller, an electric lock, door sensors, and software that holds the rules and the event log.
Key points
- A typical access-controlled door has six parts: credential, reader, controller, lock, door position switch and request-to-exit device.
- Choose fail-safe locks (unlock on power loss) for exit routes and fail-secure locks (stay locked) for security rooms, subject to your local fire code.
- Wire new readers with OSDP rather than Wiegand: it is encrypted, supervised and runs much further.
- Plan the cabling, power and fire alarm interface early; most problems come from these, not the software.
How an access control system works
A person presents a credential, such as a card or phone, at a reader. The reader sends the credential number to the controller. The controller checks it against its list of who may enter that door at that time. If access is allowed, the controller releases the lock for a few seconds and logs the event. If not, the door stays locked and the attempt is logged too.
The controller also watches the door. If the door is forced open, or held open too long, it raises an alarm.
The components, one by one
| Component | What it does | Common options |
|---|---|---|
| Credential | Identifies the person | Smart card or fob, mobile phone, PIN code, biometrics |
| Reader | Reads the credential at the door | Card reader, keypad, combined reader with keypad, biometric reader |
| Controller | Makes the decision and stores the rules | Door controller panel for 2–8 doors, or one controller per door |
| Electric lock | Holds the door shut | Electric strike, magnetic lock, electrified mortise lock |
| Door position switch | Tells the controller if the door is open | Recessed or surface magnetic contact |
| Request to exit (REX) | Lets people leave without an alarm | Motion sensor, exit push button, lock handle switch |
| Power supply | Powers the locks and controller | 12/24 V DC supply with battery backup |
| Software | Manages users, schedules and reports | On-premises server or cloud-hosted |
Credentials: cards, phones and biometrics
Older 125 kHz proximity cards are easy to copy and should be avoided for new systems. Modern 13.56 MHz smart cards use encryption and are much harder to clone. Mobile credentials on a phone are growing fast, because they are easy to issue and revoke. Biometric readers (fingerprint or face) are best for high-security rooms, often combined with a card for two-factor access.
Locks: fail-safe or fail-secure?
This is the most important safety decision in the design.
- Fail-safe: the lock releases when power is removed. Magnetic locks are always fail-safe. Used on exit routes, so people are never trapped.
- Fail-secure: the lock stays locked when power is removed, but the door can always be opened from the inside with the handle. Common for electric strikes on server rooms and stores.
Doors on escape routes usually need to release automatically when the fire alarm activates. Magnetic locks also normally need a green emergency break-glass unit beside the door. Requirements vary by country, so always confirm with the local fire code and authority.
Wiegand vs OSDP: how the reader talks to the controller
| Feature | Wiegand | OSDP |
|---|---|---|
| Encryption | None, credentials sent as plain data | AES-128 with Secure Channel |
| Communication | One-way, reader to controller | Two-way, with reader supervision |
| Maximum cable length | About 150 m (500 ft) | About 1,200 m (4,000 ft) |
| Cable | Many conductors for data, LED and buzzer | One twisted pair for data (RS-485) plus power |
Wiegand is still everywhere, but it can be tapped and replayed. For any new installation, specify OSDP readers and controllers.
Cabling an access-controlled door
Each door needs several cable runs back to its controller. A typical door has:
- Reader: a shielded multi-pair cable (OSDP needs one twisted pair plus power).
- Lock power: a 2-core cable sized for the lock current and run length, to avoid voltage drop.
- Door position switch: a 2-core cable.
- Request to exit: a 2- or 4-core cable, depending on the device.
Many installers use a composite access control cable that bundles all of these in one jacket. Newer systems use IP door controllers powered over Ethernet, which run on a single structured cabling link from the telecom room. Either way, plan the pathways and the controller location in the telecom room early, alongside the rest of the cabling.
Design checklist
- List every door, and decide the security level and lock type for each.
- Confirm fire alarm release and emergency exit rules with the authority.
- Choose credentials (avoid 125 kHz proximity cards).
- Specify OSDP readers and encrypted communication.
- Size power supplies and batteries for the total lock load.
- Plan cable routes, controller locations and network ports.
- Decide who manages users, and how cards are issued and cancelled.
- Test every door: valid card, invalid card, forced door, held-open door and fire alarm release.
Free tools for this topic
Planning the containment for door cabling? Use our free Conduit Fill Calculator and Conduit Run Planner.
Sources
OSDP and Wiegand comparison figures from the Axis Communications OSDP white paper. OSDP is published by the Security Industry Association (SIA) and as IEC 60839-11-5. Written in our own words from project experience.