Conduit & Cable Tray Fill Calculator

Check whether your data, fiber and coax cables fit in a conduit or cable tray, and find the smallest conduit size that works.

How to use it

  • Choose Conduit fill or Cable tray fill.
  • Pick the conduit size or enter the tray width and usable depth.
  • Add each cable type and its quantity. The outer diameters are typical values, so replace them with the figure from your cable datasheet.
  • Read the result: fill percentage, the allowed limit, and (for conduit) the smallest standard EMT size that fits.

How the calculation works

Each cable is treated as a circle, so its cross-sectional area is π × d² ÷ 4. The calculator adds up the area of all cables and divides it by the inside area of the conduit or tray.

For conduit, the default limits are the widely used values: 53% for one cable, 31% for two and 40% for three or more. Two cables get the lowest limit because they tend to sit side by side and jam. Many telecom designers use 40% (or less) for every run so there is room to pull more cable later, and you can choose that in the Fill rule menu.

For cable tray, a maximum of 50% fill and a cable depth of no more than 150 mm are common design limits for data cabling. Deeper bundles crush the bottom cables and trap heat, which matters for PoE.

Things the calculator cannot check

  • Bends and pull length – more than two 90° bends, or long runs, may need a larger conduit or a pull box even if the fill is fine.
  • Bend radius – larger cables such as Cat6A and high-count fiber need bigger bends and boxes.
  • Separation – keep data cables away from power, and follow your project rules for shared containment.
  • Your specification – the client spec, consultant or local code always overrides these defaults.

Related articles

Coming next: Cat6 vs Cat6A, single-mode vs multimode fiber, and how to read cable certification results.

This calculator is for planning only. Always confirm with the cable manufacturer’s datasheet and your project specification.