Free tool

Pull Box Size Calculator

Find the minimum pull box size for straight, angle or U-pulls, with every step explained and 3D views.

How does the cable pass through the box?

Note: For telecom cabling, a straight-through pull is best. It is gentle on the cable and gives the smallest box. Angle and U-pulls need much bigger boxes, so use them only when the route forces a turn.

What is a pull box?

A pull box is an empty box fitted into a conduit run so the installer can reach in and pull the cable in shorter, easier sections. Telecom runs need one when a conduit is longer than about 30 m or has more than two 90° bends between pull points.

How the size is worked out

  • Straight-through pulls: the box must be long enough for the cable to run straight across without a sharp bend. Bigger conduits need longer boxes, and each extra conduit makes the box wider.
  • Angle and U-pulls: the cable has to turn inside the box, so each wall must be at least 6 times the largest conduit away from the opposite wall, plus room for the other conduits on that wall.
  • Depth: enough to fit the largest conduit and its bushing, with room for your hands and the cable.

The calculator works out both the telecom table size and the general electrical rule, then uses whichever is bigger. Finally it rounds up to a standard box size.

Related tools

Not sure if you need a pull box at all? Use the Conduit Run Planner. To check how full a conduit is, use the Conduit & Cable Tray Fill Calculator.

Based on common telecom practice (TIA-569) and BICSI TDMM, Chapter 6, Horizontal Distribution Systems, with general electrical pull box rules for angle and U-pulls. For planning only; always follow your project specification and local codes.