OTDR trace showing connector and splice events, with Tier 1 OLTS and Tier 2 OTDR testing labels

Fiber Optic Testing: OLTS vs OTDR Explained

Fiber optic testing proves that an installed link has low enough loss to work and has no hidden faults. There are two levels: Tier 1 uses an optical loss test set (OLTS) or a light source and power meter to measure total loss, and Tier 2 adds an OTDR trace that shows where each loss happens along the cable.

Key points

  • Tier 1 (OLTS) testing is the pass/fail test for acceptance: it measures insertion loss, length and polarity.
  • Tier 2 (OTDR) testing maps every connector, splice and bend, so you can find faults and prove workmanship.
  • Test multimode at 850 and 1300 nm, single-mode at 1310 and 1550 nm.
  • Dirty connectors are the number one cause of failed tests. Inspect and clean before every test.

Why test fiber at all?

A fiber link can look perfect and still fail. A dirty connector, a tight bend behind a rack or a poor splice can each add enough loss to stop a 10G or 100G link from working. Testing catches these problems before the network goes live, and the test report becomes your proof of a good installation for the client and for the manufacturer warranty.

Tier 1 testing: OLTS and power meter

An OLTS sends a known amount of light into one end of the link and measures how much arrives at the other end. The difference is the insertion loss, in dB.

Tier 1 testing tells you three things:

  • Insertion loss at two wavelengths, compared with a pass limit.
  • Length of the link (most OLTS units measure it).
  • Polarity: that transmit at one end reaches receive at the other.

The pass limit is the calculated loss budget: the allowed loss for the fiber length plus every connector pair and splice in the link. Our free Fiber Cable Attenuation and Test Record calculates this limit for you and records results for 12 fibers.

Setting the reference: 1, 2 or 3 jumpers

Before testing, the tester is “referenced” with test cords so it knows the starting power. The method you choose changes which connectors are included in the result.

MethodWhat the result includesWhen to use it
1-jumperBoth end connections plus the fiberPreferred method for most premises links
2-jumperOne end connection plus the fiberWhen adapters don’t allow the 1-jumper method
3-jumperThe fiber only, no end connectionsSpecial cases, such as equipment cords

Always write the reference method on the test record. A result is meaningless if nobody knows how it was referenced.

Tier 2 testing: the OTDR

An OTDR (optical time domain reflectometer) works like radar. It sends short pulses of light down the fiber and measures the tiny amount reflected back over time. From this it draws a trace: a graph of loss against distance.

On a trace, you can see:

  • Connectors: a spike (reflection) followed by a step down in level.
  • Fusion splices: a small step with little or no spike.
  • Bends and stress: a step that is larger at 1550 nm than at 1310 nm.
  • The end of the fiber or a break: a large spike, then noise.

Launch and receive cables

Right after a big reflection, the OTDR is briefly “blinded”. This is called the dead zone. To see the first connector clearly, connect a launch cable (typically 100 m to 1 km long) between the OTDR and the link. Add a receive cable at the far end to measure the last connector too.

Test from both ends

A splice between two slightly different fibers can show as a “gainer” from one direction and an exaggerated loss from the other. Test from both ends and average the two results for an accurate splice loss.

OLTS or OTDR: which do you need?

QuestionOLTS (Tier 1)OTDR (Tier 2)
Does the link meet its loss budget?Yes, the most accurate answerEstimates only
Where is the fault?NoYes, to within a few meters
Are splices and connectors well made?No, total loss onlyYes, event by event
Needed for acceptance?AlwaysWhen specified, and on long or spliced links

For most building cabling, Tier 1 is the required test, and an OTDR is used when a link fails or when the specification asks for it. Long backbones and outside-plant cables with splices usually need both.

Step-by-step: testing a fiber link

  1. Calculate the loss budget for the link at both wavelengths.
  2. Inspect every end face with a fiber scope and clean it if needed.
  3. Warm up the tester, then set the reference with clean test cords.
  4. Test each fiber at both wavelengths, in both directions if specified.
  5. Compare each result with the loss budget and mark PASS or FAIL.
  6. Investigate failures with an OTDR, fix the fault, and re-test.
  7. Save the results and include them in the handover pack.

The most common reasons a fiber test fails

  • Dirty connectors: the cause of most failures. Inspect, clean, inspect again.
  • A bad reference: if results are negative or impossibly low, re-set the reference.
  • Tight bends: look for loss that is much higher at 1550 nm or 1300 nm.
  • Mismatched fiber: a 62.5 µm cord on a 50 µm link, or multimode on single-mode.
  • Poor terminations or splices: the OTDR shows which event is too high.

Free tools for this topic

Download our free fillable sheets: the Fiber Link Loss Budget and Verification sheet and the Fiber Cable Attenuation and Test Record for 12 fibers. Both calculate PASS/FAIL for you.